Quote:
Originally Posted by Boise_Chief
It could be your board but what you are describing is that the furnace isn't seeing airflow from your combustion motor. You have a small motor just inside. Is it turning on. It's fairly obvious. Also you have a little pot that has a small rubber hose tan or clear. Take one end off lightly suck and blow a few times. Replace that end and do the same with the other end. Then try turning it back on
|
Quote:
Originally Posted by Boise_Chief
No it is an airpressure switch. It gets plugged often and can cause your problem. It senses pressure when the combustion motor runs and opens the gas valve if it sees pressure. No gas no heat
|
This thread shall be forever known as the Boise_Chief appreciation thread. All I had to do was suck and blow some hose!!